C 2526 Klorinatör
DIN 19606 vacuum chlorinator — 5/10/15/25 kg/h
The most common use for vacuum chlorinators is disinfecting water in waterworks, cooling towers and water treatment plants — all of which require automated chlorinators. The C 2526 series combines classic manual chlorinators with automation elements, with remote control via standard signals.
The C 2526 is a DIN 19606-compliant vacuum chlorinator used for dosing dangerous gases such as chlorine, sulphur dioxide or ammonia. Gas escapes are impossible because pressure in all parts of the chlorinator is lower than atmospheric pressure. In standard devices the dosage is set manually and displayed on a float-type flow meter made of high-resistance glass; on devices with automatic control valve the dosage can be set remotely using standard signals. The control valve has a nozzle system specially developed for chlorine — highly chemical-resistant and insensitive to soiling.
Key features
- Vacuum technology compliant with DIN 19606
- Glass flow meter
- Highly chemical-resistant materials
- Automatic control valve (optional)
- Signal converter (optional)
- Back-pressure regulator and vacuum meter
- Wall-mounted (WL) or free-standing cabinet (SL) versions
Technical specifications
| Dosage range | 5 / 10 / 15 / 25 kg/h Cl₂ |
|---|---|
| Operating vacuum | -100 mbar |
| Required injector vacuum | -250 mbar |
| Adjustable flow range | 0 – 100% |
| Flow meter | 300 mm / 1:20 scale, ±2% accuracy |
| Vacuum meter | -1 – 0 bar, Ø63 mm, ±2.5% |
| Materials in contact with media | PVC, PMMA, Hastelloy, FPM |
| Weight | Wall device approx. 15 kg / cabinet approx. 43 kg |
| Ambient temperature | 0 – 40 °C, no direct sunlight |